GENERAL FEATURES
Capacitors of the BIORIPHASO/TF type series constitute a complete range for making of solutions for power-factor correction in MV and HV. They are designed and manufactured using the most modern technologies: ensuring long expected life and high reliability. The BIORIPHASO/TF series is in compliance with applicable standards (IEC 60871, ANSI, IEEE 18, NEMA CP-1, etc.): they are therefore suitable for installation in any environment or conditions described in the above standards. On request, we can, nevertheless, provide capacitors with special characteristic or tested as specified by the customer.

CLASSIFICATION
The various models are identified by
   • series name
   • power
   • voltage
   • typology
     • single-phase: with or without internal fuses, with single or double isolator;
     • three-phase: with delta or star connection with neutral brought out

Documents
✚ BIORIPHASO-TF

SPEC


Bioriphaso/TF Three-Phase
The three-phase capacitors are a simple and cheap solution to create groups of three-phase power factor up to 500 kvar. They are normally used for power factor correction of motors or no load MV/LV transformers. Inside the three-phase capacitors are composed of three single phase units connected in delta or star or star with neutral brought out. The three-phase capacitors for voltages up to 12 kV are usually delta connected and protected with current-limiting type fuses (HRC fuses with a high switching capacity). It’s important to use this type of fuses to prevent the explosion of the capacitor that in case of short circuit will absorb the phase to phase short-circuit system current. Capacitors with internal star connection or with neutral brought out are provided on request.

ROUTINE TESTS, TYPE TEST AND SPECIAL TEST
ICAR subjects all BIORIPHASO/TF capacitors to all routine tests required by IEC standards 60871 and it issues relevant certificates. The HV laboratory of ICAR is equipped to perform all routine tests, type tests and the special tests as foreseen for by IEC 60871.

● Routine tests:
Capacitance measurement (IEC 60871-1, art. 7) Measurement of the tangent of the loss angle (tanδ) of test capacitor (IEC 60871-1, art. 8) Voltage test between terminals (IEC 60871-1, art. 9) AC voltage test between terminals and container (IEC 60871-1, art. 10) Test of internal discharge device (IEC 60871-1, art. 11) Sealing test (IEC 60871-1, art. 12) Discharge test on internal fuses (IEC 60871-4, art 5.1.1)

● Type Test
Thermal stability test (IEC 60871-1, art. 13) Measurement of the tangent of the loss angle (tanδ) of the capacitor at elevated temperature (IEC 60871-1, art. 14) AC voltage test between terminals and container (IEC 60871-1, art. 15) Lightning impulse voltage test between terminals and container (IEC 60871-1, art. 16) Short circuit discharge test (IEC 60871-1, art. 17) Disconnecting test on internal fuses (IEC 60871-4, art. 5.3)

● Special tests
Ageing test (IEC 60871-2, art. 2.1.4) Overvoltage cycling test (IEC 60871-2, art. 2.1.3).


OPERATING CONDITIONS

• Temperature class -40/B
• Use: indoor/outdoor
• Altitude a.s.l.: 1000 m
• Frequency: 50/60 Hz

BUSHINGS
• indoor
• Voltage levels: 7.2/20/60 kV
• Creepage distance > 135 mm
• indoor/outdoor
• Voltage levels: 12/28/75 kV
• Creepage distance > 255 mm
Other voltages and powers available upon request